MAINTENANCE INSTRUCTION NO 233
OF
SILENT
DG SET 160 KVA MAKE KIRLOSKAR
INTRODUCTION:-
1. ‘REDY
POWER’ 160 KVA generator set has
been developed as a reliable source of 415V, 3phase, 50 Hertz, AC power supply,
along with control panel, fuel tank and all other associated equipment mounted
on the base frame through antivibration mounting pads various fault warning and
protection circuits with provision for automatic audio alarm, visual indication
and engine shut down have been in corporated to protect the DG set from any
damage while it is in operation. Set is provided with necessary facilities for
manual remote operation and set is suitable for (-) 10ºC to (+) 55ºC, relative
humidity 100% at all temperature, Altitude operation 4500 meter above an
climate condition: and dusty, extreme cold and hot environment.
Maintenance
is the most important factor for both the life and keeping the engine/ machine
in the best operating conditions. Preventive maintenance is more economical
than corrective repairs. Be sure to maintain engine /DG set/alternator
according to schedule given in this GMI for running in period and later in
regular interval, respectively.
This
GMI as guide line describes procedures of maintenance, lubrication, handling,
checking and adjustment. It will help the operator realize peak performance
through effective, economical and safe equipment operation. This GMI requires
to be read carefully before operating the equipment to prolong its service
life.
Generator
set has main three section parts.
a)
|
Engine
|
b)
|
Alternator
|
c)
|
Control
panel
|
ENGINE:- The prime mover of
the set is a Kirloskar make diesel engine emission complaint type 6 SL 1500 TA,
water cooled, turbocharged, after cooled,6 cylinder developing 254 BHP at 1500 Rpm. Engine speed is controlled by a
system with mechanical back up.
ALTERNATOR- The alternator used
is of brush less design, Kirloskar green make, Type KG 254 MD manufactured by
M/s Kirloskar engine Ltd and is rated for 160 KVA 415 V, 3phase 50 Hz 0.8 PF
1500 rpm.
CONTROL PANEL:- Control panel is in
corporated with all requisite facilities to control and monitor the function of
160 KVA DG set. Automatic
activated fault warning and protection system with audio and visual indication,
battery charging, and alternator for starting better is incorporated.
AIM:- The instructions are issued as guide lines for
schedule of preventive maintenance, lubrication of Generator set 160 KVA manufactured by Kirloskar Ltd for regular
attention to keep the equipment in good mechanical condition and it must be
strictly followed.
Action
by
a)
|
User Unit:
|
|
To
carry out periodic inspection and monitor regular/periodical maintenance as
laid down in this instruction and record the tasks done in the log book.
|
||
b)
|
Field Wksp (GREF)
|
|
i)
|
To carry out and monitor, maintenance
schedule and oil changes as per periodical maintenance laid down in the
maintenance instructions and to check the record of maintenance including
lubrication.
|
|
ii)
|
To advise the user unit in respect of any
lapses noticed.
|
|
c)
|
Mobile Maintenance Team:
|
|
To ensure that proper maintenance is
carried out and report accordingly to Task Force Commander and OC Fd Wksp for
necessary action.
|
4. Details: The details of
maintenance and lubrication with their periodicity are as under:-
a)
|
Daily check
|
:
|
Appx ‘A’
|
b)
|
Operating
instruction
|
:
|
Appx ‘B’
|
c)
|
Do’s and Don’ts
|
:
|
Appx ‘C’
|
d)
|
Maintenance
schedule
|
:
|
Appx ‘D’
|
e)
|
Regular maintenance
|
:
|
Appx ‘E’
|
f)
|
Technical data
|
:
|
Appx ‘F’
|
g)
|
Lubricants
|
:
|
Appx ‘G’
|
5. Please
ack receipt.
(Hari
Prakash)
|
|||||||||||||
SE (E&M) FS
|
|||||||||||||
Dir (Tech)
|
|||||||||||||
Distribution
|
for Dir Gen Border
roads
|
||||||||||||
Normal
|
|||||||||||||
Appx-‘A’
|
|||||||||||||
DAILY CHECK:-
|
|||||||||||||
1.
|
Fuel Supply
|
||||||||||||
a)
|
Check the diesel
level in this tank.
|
||||||||||||
b)
|
When filling in
fuel, be careful to add clean fuel only.
|
||||||||||||
c)
|
After prolonged
stand still, of the engine unadulterated ventilate the fuel system.
|
||||||||||||
2.
|
Oil Level
|
||||||||||||
a)
|
Check the oil level
every day before starting the engine.
|
||||||||||||
b)
|
Check the oil level
when the engine is cold and in horizontal position.
|
||||||||||||
c)
|
When a dipstick is
used, the oil level must be between the top mark and bottom mark of the
dipstick.
|
||||||||||||
3.
|
Coolant level
|
||||||||||||
a)
|
Inspect the coolant
level every day before starting.
|
||||||||||||
b)
|
If coolant has to
be added, fill in only the prescribed coolant.
|
||||||||||||
4.
|
AT TEMPRATURE BELOW
0°C:-
|
||||||||||||
a)
|
When cold starting
device is provided on engine, separate instruction for engine starting are
provided depending upon the starting aid provided based on the needs of
environmental conditions.
|
||||||||||||
b)
|
Optimum operating
range of the coolant is from 80°C to 95°C , operation below coolant temp of
80°C will result in the excessive wear of the engine, loss of the life of the
engine and increase fuel consumption.
|
||||||||||||
c)
|
Temperature above
95°C and up to 110°C as max indicate overloading of the engine or clogged
radiator and are permissible only up to a maximum time of 10 minutes.
|
||||||||||||
Appx-‘B’
|
|||||||||||||
OPERATING
INSTRUCTIONS:-
|
|||||||||||||
At the time of
initial commissioning of a new or overhaul engine and before daily starting
of the engine.
|
|||||||||||||
a)
|
Check the fuel,
coolant and oil level, replenish if necessary
|
||||||||||||
b)
|
Check electrical
and battery connections.
|
||||||||||||
c)
|
Check condition of
belt.
|
||||||||||||
d)
|
Ensure utmost
clearness when handling fuel, lubricants and coolants.
|
||||||||||||
e)
|
Check all nut and
bolts for tightness.
|
||||||||||||
For an overhauled engine or for an engine
after long periods without use,
|
|||||||||||||
a)
|
On first starting
press shut down lever in ‘Stop’ position and operate starter motor for a few
second till oil pressure is indicated and then start the engine in the normal
way.
|
||||||||||||
b)
|
Engine should be
run at rated rpm 25% load until the temp of the engine comes to normal
operating condition.
|
||||||||||||
c)
|
Over load,
continuous full load operation and continuous no load should be avoided.
|
||||||||||||
d)
|
Abrupt start and
stop of the engine should be avoided.
|
||||||||||||
e)
|
Engine load should
not exceed 70% of its prime rating.
|
||||||||||||
f)
|
Maintenance and
inspection must be accomplished thoroughly.
|
||||||||||||
g)
|
Check engine oil
level frequently.
|
||||||||||||
h)
|
Check water level
on indicator located on radiator.
|
||||||||||||
j)
|
Check battery
charging.
|
||||||||||||
k)
|
Check leakage if
any and rectify.
|
||||||||||||
CHARGING ALTERNATOR:-
|
|||||||||||||
In order to avoid
damage to the alternator, observe the following instruction while the engine
is running.
|
|||||||||||||
a)
|
Don’t disconnect
the battery or pole terminal or the cables.
|
||||||||||||
b)
|
If during operation
the battery charge lamp suddenly light, Stop the engine and rectify the fault
in the electrical system.
|
||||||||||||
c)
|
Don’t short circuit
the connections of the alternator with those of the regulator or with ground.
|
||||||||||||
COLD STARTING AIDS:-
|
|||||||||||||
Cold starting aids
facility is provided on the engine, When DG set are accepted to operate at
sites when ambient temperature goes down to 0°C and below.
|
|||||||||||||
Appx- ‘C’
|
|||||||||||||
DO’s AND DON’Ts:-
|
|||||||||||||
DO’S:-
|
|||||||||||||
1.
|
First study the operator s and
technical manual before handling or operating the power plant.
|
||||||||||||
2.
|
Ensure good ventilation around the
power plant.
|
||||||||||||
3.
|
Ensure all protective guards and
covers are securely in place before starting the DG sets.
|
||||||||||||
4.
|
Ensure proper and effective earthing
or DG set and control panel frames.
|
||||||||||||
5.
|
Be attentive to any unusual sound
from a running DG set and find out the cause of such sound.
|
||||||||||||
6.
|
Apply or remove load a gradual
manner.
|
||||||||||||
7.
|
Use only proper tool and testers
while carrying out repair and maintenance.
|
||||||||||||
8.
|
Ensure all filter elements/
strainers are replaced cleaned at recommended intervals.
|
||||||||||||
9.
|
Use only genuine parts.
|
||||||||||||
10.
|
Carry out frequent and regular
monitoring of all meters indicators while the power plant is running.
|
||||||||||||
11.
|
Clean the centrifugal cleaner at
every 250 hrs or at the time of oil changing.
|
||||||||||||
12.
|
Daily check the condition of rubber
hoses and hose clip before starting the engine. Damage hoses / clip must be
replaced immediately.
|
||||||||||||
DON’Ts
|
|||||||||||||
1.
|
Don’t
Operate the DG set with any parts of the protective guards or covers removed
or loose.
|
||||||||||||
2.
|
Don’t
switch on load immediately after starting the sets. Allow at least five minutes of no load
running.
|
||||||||||||
3.
|
Don’t
stop the engine immediately after switching off the load allow at least 10
minutes of ‘No load running’.
|
||||||||||||
4.
|
Don’t
bring a naked flame near the battery while it is on charge.
|
||||||||||||
5.
|
Don’t
run the DG set without load for long periods.
|
||||||||||||
6.
|
Don’t
load the set beyond its capacity.
|
||||||||||||
7.
|
Don’t
turn off the fuel supply to stop the engine.
|
||||||||||||
8.
|
Don’t
use the decompressor to stop the engine.
|
||||||||||||
9.
|
Don’t
try to carry out any repairs while the set is running.
|
||||||||||||
10.
|
Don’t
allow untrained persons to operate the power plant.
|
||||||||||||
11.
|
Never
try to clean and re-use the old filter inserts.
|
||||||||||||
12.
|
Don’t
tamper with FIP, concern authorize dealer if any trouble.
|
||||||||||||
Appx- ‘D’
|
|||||||||||||
MAINTENANCE
SCHEDULE FOR RUNNING -IN- PERIOD
|
|||||||||||||
DAILY:-
|
|||||||||||||
1.
|
Check engine oil
level, top up if necessary.
|
||||||||||||
2.
|
Drain sediments
from fuel tank.
|
||||||||||||
3.
|
Fill up the fuel
tank at the end of each working day.
|
||||||||||||
4.
|
Remove dust
accumulated in the dry type air filter bowl, through vacuator valve.
|
||||||||||||
5.
|
Check coolant in
the radiator, top up if required.
|
||||||||||||
6.
|
Draining of water
is absolutely necessary, if temperature below freezing point.
|
||||||||||||
7.
|
Clean radiator and
change air cooler externally every after 1200 hour’s operation.
|
||||||||||||
8.
|
Check battery
electrolyte.
|
||||||||||||
9.
|
Check the battery
terminal; apply acid proofing grease for protection against. corrosion.
|
||||||||||||
AFTER
50 HOURS:-
|
|||||||||||||
1.
|
Check engine oil.
|
||||||||||||
2.
|
Clean centrifugal
filter.
|
||||||||||||
3.
|
Change spin-on type
filter.
|
||||||||||||
4.
|
Check and tighten
fuel pipe.
|
||||||||||||
5.
|
Check valve tappet
clearance.
|
||||||||||||
6.
|
Check ‘V’ belt
tension.
|
||||||||||||
7.
|
Check electrolyte
level and specific gravity in the battery.
|
||||||||||||
8.
|
Check all
fasteners, especially those of manifolds, bends, turbo chargers, and engine mounting
and rubber hoses.
|
||||||||||||
9.
|
Check leaks, if any
and rectify.
|
||||||||||||
10.
|
Top up radiator every day before starting
the engine.
|
||||||||||||
Appx- ‘E’
|
|||||||||||||
REGULAR
MAINTENANCE
|
|||||||||||||
A. DAILY:-
|
|||||||||||||
1.
|
Check engine oil
level, top up if necessary.
|
||||||||||||
2.
|
Drain water and
sediments accumulated at the bottom of fuel tank before starting the engine.
|
||||||||||||
3.
|
Fill up the fuel
tank at the end of each working day.
|
||||||||||||
4.
|
Remove dust
accumulated in the dry type in filter bowl, through vacuator valve.
|
||||||||||||
5.
|
Check coolant in
the radiator, top up if required.
|
||||||||||||
B. AFTER 50 HRS
|
|||||||||||||
1.
|
Check engine oil
level, top up if necessary.
|
||||||||||||
2.
|
Drain water and
sediments accumulated at the bottom of fuel tank before starting the engine.
|
||||||||||||
3.
|
Fill up the fuel
tank at the end of each working day.
|
||||||||||||
4.
|
Remove dust
accumulated in the dry type in filter bowl, through vacuator valve.
|
||||||||||||
5.
|
Check coolant in
the radiator, top up if required.
|
||||||||||||
6.
|
In very dusty
condition, clean the bowl of dry type air cleaner and if necessary change the element.
|
||||||||||||
7.
|
Check ‘V’ belt
tension and adjust if required.
|
||||||||||||
8.
|
Check electrolyte
level in battery.
|
||||||||||||
9.
|
Check the cable
connection at starter, battery, dynamo/alternator and control. panel.
|
||||||||||||
C. AFTER 300 HRS
|
|||||||||||||
1.
|
Check engine oil.
|
||||||||||||
2.
|
Clean centrifugal
filter.
|
||||||||||||
3.
|
Drain sediments and
water accumulated at the bottom of fuel filter bowls.
|
||||||||||||
4.
|
Clean the filter
and sieve with clean diesel, fitted on feed pump inlet.
|
||||||||||||
5.
|
Check tightness of
fine drive pulley.
|
||||||||||||
6.
|
Replace pre-filter
and micro filter insert first at 200 hrs to 250 hrs.
|
||||||||||||
7.
|
Check and tightness
of the drive belt after every 300 hrs.
|
||||||||||||
D. AFTER 600 HRS
|
|||||||||||||
1.
|
Check engine oil
level, top up if necessary.
|
||||||||||||
2.
|
Drain water and
sediments accumulated at the bottom of fuel tank before starting. the
engine.
|
||||||||||||
3.
|
Fill up the fuel
tank at the end of each working day.
|
||||||||||||
4.
|
Remove dust
accumulated in the dry type in filter bowl, through vacuator valve.
|
||||||||||||
5.
|
Check coolant in
the radiator, top up if required.
|
||||||||||||
6.
|
In very dusty
condition, clean the bowl of dry type air cleaner and if necessary. change
the element.
|
||||||||||||
7.
|
Check V belt
tension and adjust if required.
|
||||||||||||
8.
|
Check electrolyte
level in battery.
|
||||||||||||
9.
|
Check the cable
connection at starter, battery, dynamo/alternator and control. panel.
|
||||||||||||
10.
|
Clean centrifugal
filter.
|
||||||||||||
11.
|
Drain sediments and
water accumulated at the bottom of fuel filter bowls.
|
||||||||||||
12.
|
Clean the filter
and sieve with clean diesel, fitted on feed pump inlet.
|
||||||||||||
13.
|
Check tightness of
fine drive pulley.
|
||||||||||||
14.
|
Replace pre-filter
and micro filter insert first at 200 hrs to 250 hrs.
|
||||||||||||
15.
|
Check and tightness
of the drive belt after every 300 hrs.
|
||||||||||||
16.
|
Change main oil
filter.
|
||||||||||||
17.
|
Replace the
pre-filter insert of fuel filter.
|
||||||||||||
18.
|
Change air cleaner
element.
|
||||||||||||
19.
|
Check valve tappet
clearance, adjust if required.
|
||||||||||||
20.
|
Grease fan drive pedestal.
|
||||||||||||
E. AFTER
1200 HRS
|
|||||||||||||
1.
|
Check engine oil
level, top up if necessary.
|
||||||||||||
2.
|
Drain water and
sediments accumulated at the bottom of fuel tank before starting the engine.
|
||||||||||||
3.
|
Fill up the fuel
tank at the end of each working day.
|
||||||||||||
4.
|
Remove dust
accumulated in the dry type in filter bowl, through vacuator valve.
|
||||||||||||
5.
|
Check coolant in
the radiator, top up if required.
|
||||||||||||
6.
|
In very dusty
condition, clean the bowl of dry type air cleaner and if necessary. change
the element.
|
||||||||||||
7.
|
Check V belt
tension and adjust if required.
|
||||||||||||
8.
|
Check electrolyte
level in battery.
|
||||||||||||
9.
|
Check the cable
connection at starter, battery, dynamo/alternator and control. panel.
|
||||||||||||
10.
|
Clean centrifugal
filter.
|
||||||||||||
11.
|
Drain sediments and
water accumulated at the bottom of fuel filter bowls.
|
||||||||||||
12.
|
Clean the filter
and sieve with clean diesel, fitted on feed pump inlet.
|
||||||||||||
13.
|
Check tightness of
fine drive pulley.
|
||||||||||||
14.
|
Replace pre-filter
and micro filter insert first at 200 hrs to 250 hrs.
|
||||||||||||
15.
|
Check and tightness
of the drive belt after every 300 hrs.
|
||||||||||||
16.
|
Change main oil
filter.
|
||||||||||||
17.
|
Replace the
pre-filter insert of fuel filter.
|
||||||||||||
18.
|
Change air cleaner
element.
|
||||||||||||
19.
|
Check valve tappet
clearance, adjust if required.
|
||||||||||||
20.
|
Grease fan drive
pedestal.
|
||||||||||||
21.
|
Check fuel injector
and adjust if required.
|
||||||||||||
22.
|
Check the fuel tank
thoroughly.
|
||||||||||||
23.
|
Clean radiator
externally.
|
||||||||||||
24.
|
Check thermostat
element.
|
||||||||||||
25.
|
Check electrical
unit, starter motor Dynamo/alternator, regulator etc. replace as required.
|
||||||||||||
MAINTENANCE
FUEL TANK
To
avoid ingress of dirt during operation, always use a proper full tank cap with
good rubber sealing. To minimize water contamination due to condensation of
moisture, it is advisable to fill the fuel tank in the evening, after the day
work is over. Drain the fuel tank to remove the sediment, accumulated at the
bottom of the tank. Ensure that the breather hole is not blocked. Clean the
tank thoroughly after every 1200 hrs or 6 months with diesel, do not use water
for cleaning, it will lead to rusting and scale formation.
Push
rod of the fuel feed pump is lubricated with oil from the engine or the fuel
injection pump.
CHANGE ENGINE OIL
On
new engine after first 50 hrs change the engine oil. Thereafter
every 300 hrs the oil is to be changed.
Appx ‘F’
|
|||
TECHNICAL
|
|||
Engine
|
:
|
6SL-1500TA.
|
|
Bore stroke
|
:
|
118x135.
|
|
No of cylinder
|
:
|
Six.
|
|
:
|
254.
|
||
Rpm
|
:
|
1500.
|
|
Compression ratio
|
:
|
17.5:1.
|
|
COOLING SYSTEM
|
|||
Type of cooling
|
:
|
Liquid circulation cooling with centrifugal
pump.
|
|
Thermostat
|
:
|
Heat
expensive material governor Opening begin at 95°C Full open at 95°C.
|
|
LUBRICATING SYSTEM
|
|||
Type of lubrication
|
:
|
Forced feed lubrication with gear pump.
|
|
Filters
|
:
|
2-spin on, paper filter in main stream and
1 centrifuge filter in by pass stream.
|
|
Fuel injection pump
|
:
|
Motorpal make, in-line injection pump.
|
|
Fuel filter
|
:
|
Mico make, two stages filter, first primary
filter element of left type and second
micro filter element of paper type.
|
|
TIMING GEAR
|
|||
Firing order
|
:
|
1-5-3-6-2-4.
|
|
Valve clearance
|
:
|
Intel valve 0.24 mm.
|
|
:
|
Exhaust valve 0.40 mm.
|
||
AIR SYSTEM
|
|||
Turbocharger
(For turbocharged engines)
|
:
|
Make Schwitzer.
|
|
Air Filter
|
:
|
Dry air filter with one way paper filter
cartridge and restriction indicator.
|
|
ELECTRICAL SYSTEM
|
|||
Voltage
|
:
|
24 V. (-ve earth)
|
|
Starter motor
|
:
|
Lucas / Autolek.
|
|
Alternator
|
:
|
Lucas / Autolek.
|
|